About Pressure Transmitters
More
About Pressure Switches
More
Fixed Setpoint Vacuum Switches
Prevent changes to the set vacuum that powers equipment, activates controls, or signals alarms. The setpoint on these switches isn't adjustable. They’re single pole, double throw (SPDT) and can either turn one circuit from off to on (normally open) or on to off (normally closed). NEMA 4 and 13 rated, they seal out dirt, oil, and water from washdowns. All meet American, Canadian, and European safety standards since they’re UL and C-UL recognized components and CE marked.
For technical drawings and 3-D models, click on a part number.
Setpoint, in. of Hg | Approximate Reset Point, in. of Hg | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temperature Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Quick-Disconnect Terminals | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1/4 NPT Male Pipe Connection | |||||||||||
28 | 17 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 000000 |
26 | 16 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
24 | 15 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
22 | 14 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
20 | 12 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
18 | 11 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
16 | 10 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
14 | 9 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
12 | 8 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
10 | 6 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
8 | 5 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
6 | 3 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
4 | 2 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
2 | 1 | 250 | 750 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 5 A @ 30 V DC | -20° to 220° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 4, NEMA 13 | 0000000 | 00000 |
Compact Vacuum Switches
Often built into pumps and hydraulic systems with limited space, these compact switches power equipment, activate controls, and signal alarms when they reach a set vacuum. Quickly adjust their setpoint by twisting the external ring. All are single pole, double throw (SPDT) and can be installed to turn one circuit from off to on (normally open) or from on to off (normally closed). UL listed or a UL recognized component, these switches meet American safety standards.
NEMA 1 rated switches protect against some corrosion, but they shouldn’t be used outdoors. NEMA 4 rated switches protect against corrosion and seal out dust and water from washdowns and the weather. IP65 rated switches stand up to dust and light rinses.
For technical drawings and 3-D models, click on a part number.
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point, in. of Hg | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temperature Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Quick-Disconnect Terminals | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1/4 NPT Male Pipe Connection | |||||||||||
28-6 | 4 | 14.7 | 30 | ±2% | 5 A @ 125 V AC 5 A @ 250 V AC | 0° to 165° | Brass | Air, Hydraulic Fluid, Oil, Water | NEMA 1 | 00000000 | 0000000 |
Wire Leads | |||||||||||
1/4 NPT Male Pipe Connection | |||||||||||
28-6 | 4 | 14.7 | 30 | ±2% | 5 A @ 125 V AC 5 A @ 250 V AC | 0° to 165° | Brass | Air, Hydraulic Fluid, Oil, Water | NEMA 1 | 0000000 | 000000 |
28-6 | 4 | 14.7 | 30 | ±2% | 5 A @ 125 V AC 5 A @ 250 V AC | 0° to 165° | Brass | Air, Hydraulic Fluid, Oil, Water | NEMA 4 | 00000000 | 000000 |
DIN Type A | |||||||||||
1/4 NPT Male Pipe Connection | |||||||||||
28-6 | 4 | 14.7 | 30 | ±2% | 5 A @ 125 V AC 5 A @ 250 V AC | 0° to 165° | Brass | Air, Hydraulic Fluid, Oil, Water | IP65 | 0000000 | 000000 |
Vacuum Switches
The traditional vacuum switch. When these switches reach a set vacuum, they power equipment, signal controls, or trigger alarms. They’re larger and easier to wire than our compact vacuum switches. All are single pole, double throw (SPDT) and can be installed to turn one circuit from off to on (normally open) or from on to off (normally closed). NEMA rated, they protect against some corrosion but shouldn’t be used outdoors. They all meet safety standards.
Switches with a cover protect against impact and keep dust off the switch.
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point, in. of Hg | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temperature Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Screw Terminals | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1/2 NPT Male Pipe Connection | |||||||||||
29-3 | 1 | 14.7 | 30 | ±2% | 10 A @ 125 V AC 10 A @ 250 V AC 3 A @ 480 V AC | -20° to 165° | Nickel-Plated Aluminum | Air, Hydraulic Fluid, Nitrogen, Oil, Water | NEMA 1 | 00000000 | 0000000 |
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point, in. of Hg | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temperature Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Screw Terminals | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1/4 NPT Male Pipe Connection | |||||||||||
30-0 | 2 | 0 | 50 | ±1% | 15 A @ 125 V AC 15 A @ 250 V AC 15 A @ 480 V AC 1 A @ 30 V DC 30 mA @ 125 V DC | 0° to 200° | Aluminum | Air, Hydraulic Fluid (Petroleum Based) | NEMA 1 | 0000000 | 0000000 |
Electronic Vacuum Switches for Compressed Air
Specifically made for air systems, these switches send signals to your programmable logic controller (PLC) to trigger processes when they reach a set vacuum. Use them to turn equipment on or off, activate automated controls, or signal alarms. Check the vacuum on the display and change your setpoint, reset point, scaling, and other settings using the buttons. An adjustable reset point means you can control the amount of vacuum change before the switch resets, also known as deadband or differential. Choose anywhere within the setpoint range for your reset point. All switches meet at least one American, Canadian, or European safety standard.
Switches with configurable output give you flexibility to choose between PNP, NPN, or IO Link. When using IO Link, you can remotely control and monitor your vacuum from your PLC or PC when you connect an IO Link controller (not included).
IP65 rated switches protect against dust and light rinses.
Add a square panel-mount bracket (sold separately) to mount these switches to a control panel for easy viewing and adjusting.
For technical drawings and 3-D models, click on a part number.
Digital Output | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point | Maximum Continuous Pressure, psi | No. of | Signal Type | Accuracy | Maximum Switching Current | Process Temp. Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Switches | ||||||||||||
Wire Leads—1/8 NPT Male Pipe Connection | ||||||||||||
30-0 | Adjustable | 14.7 | 1 | PNP | ±0.2% | 25 mA @ 24 V DC | 25° to 120° | Nickel-Plated Brass | Air, Argon, Nitrogen | IP40 | 0000000 | 000000 |
Configurable Digital Output | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point | Maximum Continuous Pressure, psi | No. of | Signal Type | Communication Protocol | Accuracy | Maximum Switching Current | Process Temp. Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Switches with Configurable Output | |||||||||||||
Wire Leads—1/8 NPT Male Pipe Connection | |||||||||||||
30-0 | Adjustable | 14.7 | 1 | PNP, NPN | IO Link | ±0.2% | 35 mA @ 24 V DC | 25° to 120° | Nickel-Plated Brass | Air, Argon, Nitrogen | IP65 | 0000000 | 0000000 |
For Panel Cutout | ||||
---|---|---|---|---|
Ht. | Wd. | Mounting Hole Style | Each | |
1 7/32" | 1 7/32" | Straight | 0000000 | 00000 |
Economy Vacuum Switches
Choose these switches when you need reliable switching but not high accuracy. When they reach a set vacuum, they turn equipment on and off, signal automatic controls, or trigger alarms. They are single pole, double throw (SPDT) and can be installed to turn one circuit from off to on (normally open) or from on to off (normally closed). All meet American and European safety standards since they're UL recognized components and CE marked.
For technical drawings and 3-D models, click on a part number.
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point, in. of Hg | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Process Temperature Range, °F | Connection Material | For Use With | Each | |
Spade Terminals | |||||||||
---|---|---|---|---|---|---|---|---|---|
1/4 NPT Male Pipe Connection | |||||||||
28.2-2.7 | 3 | 0 | 0 | ±5.5% | -30° to 185° | Chrome-Plated Zinc | Air, Argon, Cleaning Solutions, Diesel Fuel, Gasoline, Hydraulic Fluid, Inert Gas, Nitrogen, Oil, Oxygen, Water | 0000000 | 0000000 |
Adjustable-Reset Vacuum Switches
Control the amount of vacuum change between when these switches activate and deactivate by adjusting when they reset. Also known as adjustable deadband and differential switches, you can set the reset point anywhere within the setpoint range. Use them to power equipment, signal controls, or trigger alarms when they reach the set vacuum. They’re single pole, double throw (SPDT) and can either turn one circuit from off to on (normally open) or on to off (normally closed). All meet safety standards.
Switches with an on/off indicator let you monitor the equipment it’s controlling even when it’s out of sight.
All protect against some corrosion. NEMA 1 rated switches should only be used indoors. NEMA 4X and IP66 rated switches can be used in dirty and wet areas exposed to washdowns. NEMA 4X switches also stand up to weather and have increased protection against corrosion, similar to 304 stainless steel.
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temperature Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Screw Terminals | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1/4 NPT Female Pipe Connection | |||||||||||
24-6 | Adjustable | 11.7 | 250 | ±1% | 10 A @ 125 V AC 10 A @ 250 V AC 250 mA @ 250 V AC 500 mA @ 125 V DC | 20° to 300° | 316L Stainless Steel | Air, Diesel Fuel, Gasoline, Hydraulic Fluid, Water | NEMA 4X, IP66 | 0000000 | 0000000 |
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temperature Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Screw Terminals | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1/4 NPT Male Pipe Connection | |||||||||||
30-0 | Adjustable | 14.7 | 14.7 | ±1% | 15 A @ 120 V AC 15 A @ 240 V AC 15 A @ 480 V AC | 35° to 180° | Brass | Air, Diesel Fuel, Hydraulic Fluid, Water | NEMA 1 | 0000000 | 0000000 |
Dual-Setpoint Electronic Vacuum Switches for Compressed Air
Trigger two different processes in vacuum applications by sending signals to a programmable logic controller (PLC) when these switches reach one of their two set vacuums. Designed specifically for air systems, they can turn on a vacuum pump if the vacuum is too low or a valve if the vacuum is too high. Or use them to signal an alarm before switching off a pump. Check the vacuum on the display and change your setpoint, reset point, scaling, and other settings using the buttons. An adjustable reset means you can control the amount of pressure change before the switch resets. This pressure difference is commonly referred to as deadband and differential. Choose anywhere within the setpoint range for your reset point.
Rated IP65, these switches seal out dust and water from light rinses. They meet American, Canadian, and European safety standards since they’re UL and C-UL recognized components as well as CE marked.
Add a square panel-mount bracket (sold separately) to mount these switches to a control panel for easy viewing and adjusting.
For technical drawings and 3-D models, click on a part number.
Setpoint, in. of Hg | Approximate Difference Between Setpoint and Reset Point | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Signal Output Type | Accuracy | Maximum Switching Current | Process Temp. Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Wire Leads | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
1/8 NPT Male Pipe Connection | ||||||||||||
30-0 | Adjustable | 14.6 | 72 | PNP | ±0.2% | 35 mA @ 24 V DC | 25° to 120° | Nickel-Plated Brass | Air, Argon, Hydraulic Fluid, Inert Gas, Nitrogen, Water | IP65 | 0000000 | 0000000 |
For Panel Cutout | ||||
---|---|---|---|---|
Ht. | Wd. | Mounting Hole Style | Each | |
1 7/32" | 1 7/32" | Straight | 0000000 | 00000 |
Pressure and Vacuum Switches
Because these switches work with both positive and negative (vacuum) pressures, you can use them in applications that span both. For example, these switches can turn on a light when they reach the setpoint to indicate which pressure is flowing. They’re also often used to trigger automated controls and activate alarms. These switches are single pole, double throw (SPDT) and can either turn one circuit from off to on (normally open) or from on to off (normally closed).
NEMA 4X and IP66 rated, they’re dust tight and protected from washdowns and corrosion. All are UL and C-UL listed, CSA and CSA-US certified, and CE marked, so they meet U.S., Canadian, and European safety standards.
For technical drawings and 3-D models, click on a part number.
Setpoint | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Pressure, psi | Vacuum, in. of Hg | Approximate Difference Between Setpoint and Reset Point, psi | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temp. Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Screw Terminals | ||||||||||||
1/4 NPT Female Pipe Connection | ||||||||||||
0-15 | 30-0 | 1.5 | 15 | 250 | ±1% | 15 A @ 125 V AC 15 A @ 250 V AC 15 A @ 480 V AC 6 A @ 30 V DC 500 mA @ 125 V DC 250 mA @ 250 V DC | 20° to 300° | 316 Stainless Steel | Air, Diesel Fuel, Gasoline, Hydraulic Fluid, Water | IP66, NEMA 4X | 0000000 | 0000000 |
0-30 | 30-0 | 2.25 | 30 | 250 | ±1% | 15 A @ 125 V AC 15 A @ 250 V AC 15 A @ 480 V AC 6 A @ 30 V DC 500 mA @ 125 V DC 250 mA @ 250 V DC | 20° to 300° | 316 Stainless Steel | Air, Diesel Fuel, Gasoline, Hydraulic Fluid, Water | IP66, NEMA 4X | 0000000 | 000000 |
0-60 | 30-0 | 4 | 60 | 250 | ±1% | 15 A @ 125 V AC 15 A @ 250 V AC 15 A @ 480 V AC 6 A @ 30 V DC 500 mA @ 125 V DC 250 mA @ 250 V DC | 20° to 300° | 316 Stainless Steel | Air, Diesel Fuel, Gasoline, Hydraulic Fluid, Water | IP66, NEMA 4X | 0000000 | 000000 |
Electronic Pressure and Vacuum Switches for Compressed Air
Designed specifically for air systems, these switches send signals to your programmable logic controller (PLC) to activate controls or alarms when your system reaches a set pressure or vacuum. All meet at least one American, Canadian, or European safety standard.
Monitor pressure, setpoint, and reset point on the digital display. Use the display’s buttons to change your settings. These switches have an adjustable reset point (also called adjustable deadband or differential), so you can control the amount of pressure or vacuum change before the switch resets. Choose anywhere within the setpoint range for your reset point.
Switches with a configurable output give you flexibility to choose between PNP, NPN, or IO Link. When using IO Link, you can remotely control and monitor your vacuum from your PLC or PC when you connect an IO Link controller (not included).
IP65 rated switches protect from dust and light rinsing.
Add a panel-mounting bracket (sold separately) to mount these switches to a control panel for easy viewing and adjusting.
For technical drawings and 3-D models, click on a part number.
Setpoint | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Pressure, psi | Vacuum, in. of Hg | Approximate Difference Between Setpoint and Reset Point | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temp. Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Switches (PNP) | ||||||||||||
Wire Leads—1/8 NPT Male Pipe Connection | ||||||||||||
0-14.5 | 29-0 | Adjustable | 14.5 | 72 | ±0.2% | 25 mA @ 24 V DC | 25° to 120° | Nickel-Plated Brass | Air, Argon, Inert Gas, Nitrogen | IP40 | 0000000 | 000000 |
Switches with Configurable Output (PNP, NPN, IO Link) | ||||||||||||
Wire Leads—1/8 NPT Male Pipe Connection | ||||||||||||
0-14.5 | 29-0 | Adjustable | 14.5 | 72 | ±0.2% | 35 mA @ 24 V DC | 25° to 120° | Nickel-Plated Brass | Air, Argon, Inert Gas, Nitrogen | IP65 | 0000000 | 000000 |
For Panel Cutout | ||||
---|---|---|---|---|
Ht. | Wd. | Mounting Hole Style | Each | |
1 7/32" | 1 7/32" | Straight | 0000000 | 00000 |
Dual-Setpoint Electronic Pressure and Vacuum Switches for Compressed Air
With two setpoints, these switches trigger different actions in your air system by sending signals to a programmable logic controller (PLC) when they reach one of their set pressures or vacuums. For example, they can activate one light when a system is pressurized and another when it’s under vacuum. They have an adjustable reset, so you can control the amount of pressure change before the switch resets. This pressure difference is also called deadband or differential. Choose a reset point anywhere within the setpoint range.
Easily monitor your pressure or vacuum setpoint on the digital display. Use its buttons to adjust the settings and setpoint.
These switches are rated IP65 to seal out dust and water from light rinses. They’re CE marked, UL and C-UL recognized components, and CSA certified to meet American, Canadian, and European safety standards.
Add a panel-mounting bracket (sold separately) to mount switches to a control panel for easy viewing and adjusting.
For technical drawings and 3-D models, click on a part number.
Setpoint | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Pressure, psi | Vacuum, in. of Hg | Approximate Difference Between Setpoint and Reset Point | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Signal Output Type | Accuracy | Maximum Switching Current | Process Temp. Range, °F | Connection Material | For Use With | Environmental Rating | Each | |
Wire Leads | |||||||||||||
1/8 NPT Male Pipe Connection | |||||||||||||
0-14.5 | 29-0 | Adjustable | 14.5 | 72 | PNP | ±0.2% | 35 mA @ 24 V DC | 25° to 120° | Nickel-Plated Brass | Air, Argon, Inert Gas, Nitrogen | IP65 | 0000000 | 0000000 |
For Panel Cutout | ||||
---|---|---|---|---|
Ht. | Wd. | Mounting Hole Style | Each | |
1 7/32" | 1 7/32" | Straight | 0000000 | 00000 |
Sanitary Pressure and Vacuum Switches
When these 3-A certified switches reach a set pressure or vacuum, they trigger controls and alarms in food-processing, pharmaceutical, and biotech lines. They have a sleeve to shield internal parts from water and contaminants. Their surfaces are polished and their seams are continuously welded, so cleaning is easy and there’s little room for bacteria to grow. Made of 316 stainless steel, these switches stand up to harsh cleaners and sanitizers without rusting. Rated IP67 and NEMA 6, they’re dust tight and protected from washdowns and temporary submersion.
They connect using the same quick-clamp fittings (also known as tri-clamp fittings) that are common in sanitary lines, because they’re easy to take apart for cleaning. This end has a diaphragm that protects from corrosion and covers threads to keep them clean. The diaphragm is filled with 99.5% pure USP food-grade glycerin, reducing the risk of contamination if the diaphragm fails. The serial number is laser etched on the diaphragm to reduce crevices.
Twist the adjustable setpoint ring to make quick changes. These switches are single pole, double throw (SPDT) and can be installed to turn one circuit from off to on (normally open) or from on to off (normally closed).
All have a certificate with a traceable lot number and material test report.
Setpoint | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Pressure, psi | Vacuum, in. of Hg | Approximate Difference Between Setpoint and Reset Point, psi | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Accuracy | Maximum Switching Current | Process Temp. Range, °F | Connection Material | For Use With | Specifications Met | Each | |
Wire Leads | ||||||||||||
1 1/2" Tube OD Quick-Clamp Connection | ||||||||||||
0-15 | 30-0 | 3 | 15 | 1,000 | ±2% | 5 A @ 125 V AC 5 A @ 250 V AC 3 A @ 28 V DC | -40° to 212° | 316 Stainless Steel | Argon, Beverage, Diesel Fuel, Food, Gasoline, Hydraulic Fluid, Inert Gas, Natural Gas, Nitrogen, Oil, Oxygen, Water | 3-A Certified 74-07, UL Listed | 00000000 | 0000000 |
2" Tube OD Quick-Clamp Connection | ||||||||||||
0-15 | 30-0 | 3 | 15 | 1,000 | ±2% | 5 A @ 125 V AC 5 A @ 250 V AC 3 A @ 28 V DC | -40° to 212° | 316 Stainless Steel | Argon, Beverage, Diesel Fuel, Food, Gasoline, Hydraulic Fluid, Inert Gas, Natural Gas, Nitrogen, Oil, Oxygen, Water | 3-A Certified 74-07, UL Listed | 00000000 | 000000 |
Pressure and Vacuum Transmitters with Digital Display
- For Use With: Air, Argon, Diesel Fuel, Hydraulic Fluid, Nitrogen, Water
- Accuracy: ±1%
- Pipe Connection Type: Threaded
- Housing Material: Glass-Reinforced Polyester
- Connection Material: 316L Stainless Steel
- Temperature Range: -10° to 175°F
Monitor and control vacuum pumps, air compressors, and hydraulics while viewing readings and warnings on the display. These transmitters, also called transducers, have two outputs, so you can program them to work as a transmitter, a switch, or both. When they reach their setpoint, they send electrical signals to your programmable logic controller (PLC) to trigger actions in your system. Adjust their reset point anywhere within the setpoint range. To change settings and receive error messages remotely from your PLC or computer, program one of the outputs to use IO Link. You need an IO-Link controller (not included) to connect to your interface.
Buttons on the display let you change your setpoint, measuring range, and other settings. To quickly tell the status of your process, you can program the color of the display to red and green. LEDs on the corners also notify you of your output’s switching status. Rotate the head to view the display from the best angle.
You must calibrate your PLC in order for it to interpret signals from these transmitters. As pressure increases, the output signal from the transmitter will increase. These transmitters only give accurate readings within the rated pressure or vacuum range.
All have an M12 plug to connect to M12 Connectors. When using both switching outputs and an IO-Link controller, they require four wires to connect. For their 4-20mA analog output, they need two wires to connect. View switch wiring diagrams by selecting a part number and clicking Product Detail.
To withstand wet environments, these transmitters have a 316L stainless steel connection and are IP rated. Their IP ratings also mean they’re dust tight and stand up to spraying water and brief submersion. UL and C-UL listed as well as CE marked, they meet strict American, Canadian, and European safety standards.
For technical drawings and 3-D models, click on a part number.
Setpoint Range | Configurable Analog Transmitter/Digital Switch Output | Configurable Digital Switch Output | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Pressure Range, psi | Vacuum Range, in. of Hg | Max. Continuous and Short-Term Pressure, psi | Pressure, psi | Vacuum, in. of Hg | Input Voltage | Pipe Size | Ht. | Wd. | No. of | Current | Signal Type | No. of | Signal Type | Scale | Each | |
NPT Female | ||||||||||||||||
0-14.5 | 29.5-0 | 145 | 0-14.5 | 29.5-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | in. of H2O, in. of Hg, kPa, mbar, psi | 0000000 | 0000000 |
0-145 | 29.7-0 | 1,085 | 0-145 | 29.7-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
0-362.5 | 29.5-0 | 2,175 | 0-362.5 | 29.5-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
NPT Male | ||||||||||||||||
0-14.5 | 29.5-0 | 145 | 0-14.5 | 29.5-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | in. of H2O, in. of Hg, kPa, mbar, psi | 0000000 | 000000 |
0-145 | 29.7-0 | 1,085 | 0-145 | 29.7-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
0-360 | 29.5-0 | 2,175 | 0-360 | 29.5-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
BSPP Female | ||||||||||||||||
0-7.3 | 14.8-0 | 145 | 0-7.3 | 14.8-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | in. of H2O, kPa, mbar, psi | 0000000 | 000000 |
0-14.5 | 1.4-0 | 145 | 0-14.5 | 1.4-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | in. of H2O, kPa, mbar, psi | 0000000 | 000000 |
0-14.5 | 29.5-0 | 145 | 0-14.5 | 29.5-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | in. of H2O, in. of Hg, kPa, mbar, psi | 0000000 | 000000 |
0-87 | 29.5-0 | 600 | 0-87 | 29.5-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
0-145 | 29.7-0 | 1,085 | 0-145 | 29.7-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
0-360 | 29.5-0 | 2,175 | 0-360 | 29.5-0 | 18-30V DC | 1/4 | 3 9/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
BSPP Male | ||||||||||||||||
0-7.3 | 14.8-0 | 145 | 0-7.3 | 14.8-0 | 18-30V DC | 1/4 | 3 11/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
0-14.5 | 1.4-0 | 145 | 0-14.5 | 1.4-0 | 18-30V DC | 1/4 | 3 11/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
0-14.5 | 29.5-0 | 145 | 0-14.5 | 29.5-0 | 18-30V DC | 1/4 | 3 11/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | in. of H2O, in. of Hg, kPa, mbar, psi | 0000000 | 000000 |
0-87 | 29.5-0 | 600 | 0-87 | 29.5-0 | 18-30V DC | 1/4 | 3 11/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
0-145 | 29.7-0 | 1,085 | 0-145 | 29.7-0 | 18-30V DC | 1/4 | 3 11/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
0-360 | 29.5-0 | 145 | 0-360 | 29.5-0 | 18-30V DC | 1/4 | 3 11/16" | 1 3/8" | 1 | 4-20mA | NPN, PNP | 1 | NPN, PNP | bar, MPa, psi | 0000000 | 000000 |
Pressure and Vacuum Transmitters for Compressed Air
- For Use With: Air, Argon, Nitrogen
- Accuracy: ±0.2%
- Connection: See table
- Housing Material: Polybutylene Plastic
- Connection Material: Nickel-Plated Brass
- Temperature Range: 25° to 120° F
Specifically made for compressed air and gas systems, these transmitters remotely monitor pressure and vacuum. Also known as transducers, they convert both pressure and vacuum into an electrical signal that can be interpreted by receiving devices, such as remote displays, and motor speed controls. They also have two digital PNP switch outputs that you can connect to your programmable logic controller (PLC) to activate automated controls or alarms when a set pressure or vacuum is reached. Change settings with the buttons on the digital display.
For your receiving device to interpret the signal from the transmitter, you will need to calibrate it for the transmitter's pressure or vacuum range and output signal. As pressure increases, the output signal from the transmitter will increase. Transmitters will only provide accurate readings within the rated pressure or vacuum range.
UL and C-UL recognized components, CSA certified, and CE marked, they meet American, Canadian, and European safety standards.
Transmitters with current output connect using two wires. The same wire is used to send a signal to the receiver and to power the transmitter. Current doesn’t lose signal over long distances and isn’t affected by electrical interference from other devices.
Transmitters with voltage output connect using three wires. Two wires connect to the power supply, and a separate wire sends a signal to the receiver. The receiver and the transmitter share a common ground wire back to the power supply.
Add a panel-mounting bracket (sold separately) to mount these switches to a control panel for easy viewing and adjusting.
For technical drawings and 3-D models, click on a part number.
Analog Transmitter Output | Digital Switch Output | Setpoint Range | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Signal | No. of | Signal Type | No. of | Pressure Range, psi | Vacuum Range, in. of Hg | Maximum Continuous Pressure, psi | Maximum Short-Term Pressure, psi | Pressure, psi | Vacuum, in. of Hg | Input Voltage | Ht. | Wd. | Environmental Rating | Each | |
Wire Leads | |||||||||||||||
1/8 NPT Male Pipe Connection | |||||||||||||||
4-20mA | 1 | PNP | 2 | 0-14.5 | 29-0 | 14.5 | 72 | 0-14.5 | 29-0 | 12-24V DC | 1 3/16" | 1 3/16" | IP40 | 0000000 | 000000 |
1-5V DC | 1 | PNP | 2 | 0-14.5 | 29-0 | 14.5 | 72 | 0-14.5 | 29-0 | 12-24V DC | 1 3/16" | 1 3/16" | IP40 | 0000000 | 00000 |
1/4" OD Push-to-Connect Tube Connection | |||||||||||||||
4-20mA | 1 | PNP | 2 | 0-14.5 | 29-0 | 14.5 | 72 | 0-14.5 | 29-0 | 12-24V DC | 1 3/16" | 1 3/16" | IP40 | 0000000 | 00000 |
1-5V DC | 1 | PNP | 2 | 0-14.5 | 29-0 | 14.5 | 72 | 0-14.5 | 29-0 | 12-24V DC | 1 3/16" | 1 3/16" | IP40 | 0000000 | 00000 |
For Panel Cutout | ||||
---|---|---|---|---|
Ht. | Wd. | Mounting Hole Style | Each | |