Fixed-Setpoint Threaded Temperature Switches
Set to actuate at a specific temperature, these switches are easy to setup and prevent changes to the setpoint. They have a threaded probe, so they install directly into tanks, pipelines, and other process components to turn equipment on and off at a set temperature.
Narrow differential switches reset after a small temperature change in the opposite direction of your switch's actuation. For example, in a rising-actuation switch, they reset after the temperature falls 3° below the setpoint. Use them in systems where temperature changes slowly and where you need precision. Wide differential switches reset after the temperature significantly decreases (approximately 15%) below the setpoint. Use them in systems that cannot handle frequent power cycling.
Rising actuation switches activate when the temperature rises to the setpoint and then reset when the temperature falls below the setpoint. Choose rising actuation SPST-NO switches to power a cooler or trigger an alarm.
Falling actuation switches activate when the temperature falls to the setpoint and then reset when the temperature rises above the setpoint. Choose falling actuation SPST-NO switches to power a heater or activate an alarm.
All switches are NEMA 4 and 13 rated to seal out dirt, oil, and water from washdowns. IP67 rated switches stand up to temporary submersion. UL and C-UL listed switches meet U.S. and Canadian safety standards.
For technical drawings and 3-D models, click on a part number.
Probe | SPST-NO | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
Actuation Point, °F | Actuation Tolerance | Approx. Difference Between Setpoint and Reset Point, °F | Max. Switching Current @ Voltage (Electrical Phase) | Dia. | Lg. | Max. Pressure, psi | Environmental Rating | Specifications Met | Each | |
Threaded Brass Probe—1/2 NPT Male | ||||||||||
Narrow Differential Range Sensitivity—Rising Actuation | ||||||||||
40° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 000000 |
60° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
80° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
100° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
120° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
140° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
160° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
180° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
200° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
220° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
240° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
260° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
280° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
300° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
Narrow Differential Range Sensitivity—Falling Actuation | ||||||||||
40° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
60° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
80° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
100° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
120° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
140° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
160° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
180° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
200° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
220° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
240° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
260° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
280° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
300° | ±5° F | 3° | 6 A @ 120 V AC (Single) 4 A @ 24 V DC (Single) | 3/8" | 1/2" | 5,000 | NEMA 4, NEMA 13 | UL Recognized Component, C-UL Recognized Component | 0000000 | 00000 |
Wide Differential Range Sensitivity—Rising Actuation | ||||||||||
50° | ±7° F | 8° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
75° | ±7° F | 12° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
100° | ±7° F | 15° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
125° | ±7° F | 19° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
150° | ±7° F | 23° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
175° | ±7° F | 27° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
200° | ±7° F | 30° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
225° | ±7° F | 34° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
250° | ±7° F | 38° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
275° | ±7° F | 42° | 15 A @ 125 V AC (Single) 10 A @ 250 V AC (Single) | 11/16" | 1/2" | 1,000 | IP67, NEMA 4, NEMA 13 | __ | 0000000 | 00000 |
Compact Threaded Temperature Switches
Since these switches don’t have a housing above the probe, they are often used in tight spaces and low-clearance areas. The threaded probe installs directly into tanks, pipelines, and other process components to turn heating equipment on or off at a specified temperature. Use the adjustment screw to set the actuation point. All switches are SPST (single pole, single throw) and control one circuit.
Normally open switches turn the circuit from off to on.
For technical drawings and 3-D models, click on a part number.
Probe | 1 Off (Normally Open) | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
Pipe Size | Temp. Range, °F | Actuation Tolerance | Electrical Phase | Max. Switching Current @ Voltage | Dia. | Lg. | Material | Insulation Material | Each | |
NPT Male Threaded | ||||||||||
3/8 | -100° to 600° | ±2% | Single | 5 A @ 120 V AC 3 A @ 240 V AC 1 A @ 120 V DC | 1/2" | 2" | Stainless Steel | Fiberglass | 0000000 | 0000000 |
1/2 | -100° to 600° | ±2% | Single | 10 A @ 120 V AC 5 A @ 240 V AC 2 A @ 120 V DC | 5/8" | 3" | Stainless Steel | Fiberglass | 0000000 | 000000 |
NPT Male × NPT Male Threaded | ||||||||||
3/8 × 3/8 | -100° to 600° | ±2% | Single | 5 A @ 120 V AC 3 A @ 240 V AC 1 A @ 120 V DC | 1/2" | 2" | Stainless Steel | Fiberglass | 0000000 | 000000 |
1/2 × 1/2 | -100° to 600° | ±2% | Single | 10 A @ 120 V AC 5 A @ 240 V AC 2 A @ 120 V DC | 5/8" | 3" | Stainless Steel | Fiberglass | 0000000 | 000000 |
Insertion Temperature Switches
Install the probe directly into drilled and reamed holes to turn heating equipment on or off at a specified temperature. Use the adjustment screw to set the actuation point. All switches are SPST (single pole, single throw) and control one circuit.
Normally open switches turn the circuit from off to on.
For technical drawings and 3-D models, click on a part number.
Probe | Material | 1 Off (Normally Open) | |||||||
---|---|---|---|---|---|---|---|---|---|
Lg. | Dia. | Temp. Range, °F | Actuation Tolerance | Max. Switching Current | Electrical Phase | Insulation | Probe | Each | |
2 1/2" | 1/2" | -100° to 600° | ±2% | 5 A @ 120 V AC 3 A @ 240 V AC 1 A @ 120 V DC | Single | Fiberglass | Stainless Steel | 0000000 | 000000 |
3 5/8" | 5/8" | -100° to 600° | ±2% | 10 A @ 120 V AC 5 A @ 240 V AC 2 A @ 120 V DC | Single | Fiberglass | Stainless Steel | 0000000 | 00000 |
Washdown Autotuning Temperature Controllers
The faceplate on these controllers is sealed to meet NEMA 4X and IP66 for protection in washdown environments with splashing water, corrosive liquid, and dust. The rear case meets IP20, which prevents objects about the size of a finger from coming into contact with a live circuit.
Because they have proportional-integral-derivative (PID) software, these controllers are ideal for turning heating equipment on and off in systems with rapid, unpredictable, and complex temperature changes. They help you achieve precise and stable temperature control with fuzzy logic that learns system behavior and automatically compensates for changes. Use the autotuning function to cycle and identify the ideal PID variables for your system to achieve the most precise control. These controllers read temperature with a highly sensitive thermocouple probe (sold separately) in critical process applications. All fit into instrument panels with DIN cutouts. Use the keypad to adjust the actuation point, reset point, and other settings.
Controllers with automatic reset switch off and on again automatically as the temperature fluctuates. Controllers with automatic/manual reset give you the choice to have machines turn back on either automatically when the temperature fluctuates, or you can manually reset their switch. When set to manual they shut down your machine when it gets too hot to protect equipment and personnel. They won’t turn the machine back on until you reset their switch. They have a second output to actuate an alarm or another simple device.
Mechanical relay outputs actuate circuits directly. Single pole, single throw (SPST) relays turn one circuit from off to on (normally open). Single pole, double throw (SPDT) relays can be set to turn the circuit from off to on (normally open) or from on to off (normally closed).
Solid state relay outputs send a pulse signal to directly control an external solid-state relay (not included). They have a longer service life than mechanical and signal relays. Use them for more precise and rapid control switching than mechanical relays.
Analog signal outputs send 4-20 mA current to actuate equipment on a current loop. They are typically used with SRC (silicon controlled rectifier) power controllers (not included) for some of the highest precision control.
DIN-rail/surface-mount adapters (sold separately) mount 1/16 DIN controllers to a surface.
DIN cutout adapters (sold separately) convert larger cutouts to fit 1/16 DIN controllers.
For technical drawings and 3-D models, click on a part number.
Mechanical Relay | |||||||||
---|---|---|---|---|---|---|---|---|---|
Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | For Probe Type | Reset Type | Input Voltage Range | Environmental Rating | Each | |
1/32 DIN—For 7/8" × 1 3/4" Panel Cutout | |||||||||
1 | Heating—One Mechanical Relay | Heating—SPST-NO | Heating—3 A @ 220 V AC | Thermocouple | Automatic | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 0000000 |
1/16 DIN—For 1 3/4" × 1 3/4" Panel Cutout | |||||||||
3 | Heating—One Mechanical Relay Alarm—Two Mechanical Relays | Heating—SPST-NO Alarm—SPST-NO | Heating—3 A @ 250 V AC Alarm—1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 000000 |
1/8 DIN—For 3 3/4" × 1 3/4" Panel Cutout | |||||||||
3 | Heating—One Mechanical Relay Alarm—Two Mechanical Relays | Heating—SPDT Alarm—SPST-NO | Heating—5 A @ 250 V AC Alarm—1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 000000 |
1/4 DIN—For 3 3/4" × 3 3/4" Panel Cutout | |||||||||
3 | Heating—One Mechanical Relay Alarm—Two Mechanical Relays | Heating—SPDT Alarm—SPST-NO | Heating—3 A @ 250 V AC Alarm—1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 000000 |
Mechanical Relay | |||||||||
---|---|---|---|---|---|---|---|---|---|
Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | For Probe Type | Reset Type | Input Voltage Range | Environmental Rating | Each | |
1/16 DIN—For 1 3/4" × 1 3/4" Panel Cutout | |||||||||
3 | Heating—One 12V DC Solid State Relay Drive Alarm—Two Mechanical Relays | SPST-NO | 1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 0000000 |
1/8 DIN—For 3 3/4" × 1 3/4" Panel Cutout | |||||||||
3 | Heating—One 12V DC Solid State Relay Drive Alarm—Two Mechanical Relays | SPST-NO | 1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 000000 |
1/4 DIN—For 3 3/4" × 3 3/4" Panel Cutout | |||||||||
3 | Heating—One 12V DC Solid State Relay Drive Alarm—Two Mechanical Relays | SPST-NO | 1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 000000 |
Mechanical Relay | |||||||||
---|---|---|---|---|---|---|---|---|---|
Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | For Probe Type | Reset Type | Input Voltage Range | Environmental Rating | Each | |
1/16 DIN—For 1 3/4" × 1 3/4" Panel Cutout | |||||||||
3 | Heating—One 4-20 mA Analog Signal Alarm—Two Mechanical Relays | SPST-NO | 1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 0000000 |
1/8 DIN—For 3 3/4" × 1 3/4" Panel Cutout | |||||||||
3 | Heating—One 4-20 mA Analog Signal Alarm—Two Mechanical Relays | SPST-NO | 1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 000000 |
1/4 DIN—For 3 3/4" × 3 3/4" Panel Cutout | |||||||||
3 | Heating—One 4-20 mA Analog Signal Alarm—Two Mechanical Relays | SPST-NO | 1 A @ 250 V AC | RTD, Thermocouple | Automatic, Manual | 100V AC to 240V AC | IP20, IP66, NEMA 4X | 0000000 | 000000 |
Mounting | ||||
---|---|---|---|---|
Fasteners Included | Screw Size | No. of Holes | Each | |
No | No. 6 | 2 | 000000000 | 000000 |
Autotuning Temperature Controllers
Ideal in systems with rapid, unpredictable, or complex temperature changes, these controllers turn heating equipment on and off using a proportional-integral-derivative (PID) control algorithm to make fine adjustments, giving you the most precise and stable temperature control. They work similarly to proportional controllers but gather more variables to calculate the most effective way to return to the target temperature and avoid overshooting. They also have fuzzy logic to learn your system's behavior and compensate as needed. Use the autotuning function to have the controller cycle and identify the ideal PID variables for your system. You can also manually select the PID variables. These controllers read temperature with a highly sensitive thermocouple or RTD probe (both not included) in critical process applications. Since they reset automatically, they switch off and on again as the temperature fluctuates. All fit into instrument panels with DIN cutouts. Use the keypad to adjust the actuation point, reset point, other settings.
All meet American, Canadian, and European safety standards.
Mechanical relay outputs actuate circuits directly. All are single pole, single throw (SPST) relays and turn one circuit from off to on (normally open). Solid state relay drive outputs send a pulse signal to directly control an external solid state relay (not included). They have a longer service life than mechanical and signal relays. Use them for more precise and rapid control switching than mechanical relays. Analog signal outputs are typically used with SRC (silicon controlled rectifier) power controllers (not included) for some of the highest precision control.
Alarm outputs can also be configured to actuate simple devices.
IP20 rated controllers prevent objects about the size of a finger from coming into contact with a live circuit. IP50 rated controllers protect against dust.
DIN-rail/surface-mount adapters (sold separately) mount 1/16 DIN controllers to a DIN rail or surface.
DIN cutout adapters (sold separately) convert larger cutouts to fit 1/16 DIN controllers.
Mechanical Relay | |||||||||
---|---|---|---|---|---|---|---|---|---|
Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | For Probe Type | Reset Type | Input Voltage Range | Environmental Rating | Each | |
1/32 DIN–For 7/8" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
1 | Heating—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 0000000 |
3 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/16 DIN–For 1 3/4" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
1 | Heating—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 000000 |
2 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
3 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 000000 |
3 | Heating/Cooling—One Mechanical Relay Alarm—Two Mechanical Relays | SPST-NO | 5 A @ 110 V AC | RTD, Thermocouple | Automatic | 90V AC to 264V AC | __ | 00000000 | 000000 |
4 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—Two Mechanical Relays | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 000000 |
1/8 DIN–For 1 3/4" Ht. × 3 5/8" Wd. Panel Cutout | |||||||||
1 | Heating—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 000000 |
3 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/8 DIN–For 3 5/8" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
1 | Heating—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 000000 |
3 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
3/16 DIN–For 2 11/16" Ht. × 2 11/16" Wd. Panel Cutout | |||||||||
1 | Heating—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 000000 |
3 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/4 DIN–For 3 5/8" Ht. × 3 5/8" Wd. Panel Cutout | |||||||||
1 | Heating—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 000000 |
3 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
4 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—Two Mechanical Relays | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 000000000 | 000000 |
4 | Heating/Cooling—Two Mechanical Relays Alarm—Two Mechanical Relays | SPST-NO | 5 A @ 110 V AC | RTD, Thermocouple | Automatic | 90V AC to 264V AC | __ | 00000000 | 000000 |
Mechanical Relay | |||||||||
---|---|---|---|---|---|---|---|---|---|
Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | For Probe Type | Reset Type | Input Voltage Range | Environmental Rating | Each | |
1/32 DIN–For 7/8" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
3 | Heating—One 14V DC Solid State Relay Drive Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 0000000 |
1/16 DIN–For 1 3/4" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
2 | Heating—One 14V DC Solid State Relay Drive Cooling/Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
3 | Heating—One 14V DC Solid State Relay Drive Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/8 DIN–For 1 3/4" Ht. × 3 5/8" Wd. Panel Cutout | |||||||||
3 | Heating—One 14V DC Solid State Relay Drive Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/8 DIN–For 3 5/8" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
3 | Heating—One 14V DC Solid State Relay Drive Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
3/16 DIN–For 2 11/16" Ht. × 2 11/16" Wd. Panel Cutout | |||||||||
3 | Heating—One 14V DC Solid State Relay Drive Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/4 DIN–For 3 5/8" Ht. × 3 5/8" Wd. Panel Cutout | |||||||||
3 | Heating—One 14V DC Solid State Relay Drive Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
4 | Heating—One 14V DC Solid State Relay Drive Cooling/Alarm—One Mechanical Relay Alarm—Two Mechanical Relays | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
Mechanical Relay | |||||||||
---|---|---|---|---|---|---|---|---|---|
Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | For Probe Type | Reset Type | Input Voltage Range | Environmental Rating | Each | |
1/32 DIN–For 7/8" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
3 | Heating—One 4-20 mA Analog Signal Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 0000000 |
1/16 DIN–For 1 3/4" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
2 | Heating—One 4-20 mA Analog Signal Cooling/Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/8 DIN–For 1 3/4" Ht. × 3 5/8" Wd. Panel Cutout | |||||||||
3 | Heating—One 4-20 mA Analog Signal Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/8 DIN–For 3 5/8" Ht. × 1 3/4" Wd. Panel Cutout | |||||||||
3 | Heating—One 4-20 mA Analog Signal Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
3/16 DIN–For 2 11/16" Ht. × 2 11/16" Wd. Panel Cutout | |||||||||
3 | Heating—One 4-20 mA Analog Signal Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | IP20, IP50 | 00000000 | 000000 |
1/4 DIN–For 3 5/8" Ht. × 3 5/8" Wd. Panel Cutout | |||||||||
3 | Heating/Cooling—One 4-20 mA Analog Signal Alarm—Two Mechanical Relays | SPST-NO | 5 A @ 110 V AC | RTD, Thermocouple | Automatic | 90V AC to 264V AC | __ | 00000000 | 000000 |
Mounting | ||||
---|---|---|---|---|
Fasteners Included | Screw Size | No. of Holes | Each | |
No | No. 6 | 2 | 000000000 | 000000 |
DIN-Rail-Mount Autotuning Temperature Controllers
Mount these temperature controllers directly onto DIN rail for controlling systems with rapid, unpredictable, or complex temperature changes. They turn heating equipment on and off using a proportional-integral-derivative (PID) control algorithm to make fine adjustments, giving you the most precise and stable temperature control. All work similarly to proportional controllers but gather more variables to calculate the most effective way to return to the target temperature and avoid overshooting. They also have fuzzy logic to learn your system's behavior and compensate as needed. Use the autotuning function to have the controller cycle and identify the ideal PID variables for your system. These controllers read temperature with a highly sensitive thermocouple or RTD probe (both not included) in critical process applications. Since they reset automatically, they switch off and on again as the temperature fluctuates. Use the keypad to adjust the actuation point, reset point, and other settings.
All meet American, Canadian, and European safety standards.
Mechanical relay outputs actuate circuits directly. All are single pole, single throw (SPST) relays and turn one circuit from off to on (normally open). Alarm outputs can be configured to actuate alarms or other simple devices. Those with cooling/alarm outputs can also be used to turn cooling equipment on or off at a specified temperature.
For technical drawings and 3-D models, click on a part number.
Mechanical Relay | |||||||||
---|---|---|---|---|---|---|---|---|---|
Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | For Probe Type | Reset Type | Input Voltage Range | Environmental Rating | Each | |
1 | Heating—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | NEMA 1 | 0000000 | 0000000 |
3 | Heating—One Mechanical Relay Cooling/Alarm—One Mechanical Relay Alarm—One Mechanical Relay | SPST-NO | 2 A @ 240 V AC | RTD, Thermocouple | Automatic | 90V AC to 250V AC | NEMA 1 | 0000000 | 000000 |
Benchtop Autotuning Temperature Controllers
Built into an enclosure, these temperature controllers are protected when sitting on your workbench. Ideal in systems with rapid, unpredictable, or complex temperature changes, they turn heating equipment on and off using a proportional-integral-derivative (PID) control algorithm to make fine adjustments, giving you the most precise and stable temperature control. All work similarly to proportional controllers but gather more variables to calculate the most effective way to return to the target temperature and avoid overshooting it. They also have fuzzy logic to learn your system's behavior and compensate as needed. Use the autotuning function to have the controller cycle and identify the ideal PID variables for your system. These controllers read temperature with a highly sensitive thermocouple probe in critical process applications. Since they reset automatically, they switch off and on again as the temperature fluctuates. Use the keypad to adjust the actuation point, reset point, and other settings.
The controllers have mechanical relay outputs that actuate circuits directly. All are single pole, single throw (SPST-NO) relays and turn one circuit from off to on (normally open).
Controllers with high-limit control let you attach a second thermocouple probe to take the temperature of your heating equipment. If your equipment reaches the high limit, these controllers shut down your heating equipment and won't let it turn back on until you manually reset it, improving the safety of your system.
Controllers with two control zones let you independently turn heating equipment on and off in two separate areas, each with their own thermocouple input and heating control output.
For technical drawings and 3-D models, click on a part number.
5-20 | |
6-20 |
Mechanical Relay | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
For Thermocouple Probe Type | Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | Reset Type | Input Voltage | NEMA Style | Cord Lg., ft. | Ht. | Wd. | Dp. | Environmental Rating | Each | |
J | 1 | Heating—One Mechanical Relay | SPST-NO | 16 A @ 120 V AC | Automatic | 120V AC | 5-20 | 5 | 5" | 5" | 11" | IP50 | 0000000 | 0000000 |
J | 1 | Heating—One Mechanical Relay | SPST-NO | 16 A @ 240 V AC | Automatic | 240V AC | 6-20 | 5 | 5" | 5" | 11" | IP50 | 0000000 | 000000 |
K | 1 | Heating—One Mechanical Relay | SPST-NO | 16 A @ 120 V AC | Automatic | 120V AC | 5-20 | 5 | 5" | 5" | 11" | IP50 | 00000000 | 000000 |
K | 1 | Heating—One Mechanical Relay | SPST-NO | 16 A @ 240 V AC | Automatic | 240V AC | 6-20 | 5 | 5" | 5" | 11" | IP50 | 00000000 | 000000 |
Mechanical Relay | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
For Thermocouple Probe Type | Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | Reset Type | Input Voltage | NEMA Style | Cord Lg., ft. | Ht. | Wd. | Dp. | Environmental Rating | Each | |
J—Heating K—High Limit | 1 | Heating—One Mechanical Relay | SPST-NO | 16 A @ 120 V AC | Automatic, Manual | 120V AC | 5-20 | 5 | 5" | 8 1/2" | 11" | IP50 | 00000000 | 000000000 |
K—Heating K—High Limit | 1 | Heating—One Mechanical Relay | SPST-NO | 16 A @ 120 V AC | Automatic, Manual | 120V AC | 5-20 | 5 | 5" | 8 1/2" | 11" | IP50 | 00000000 | 00000000 |
Mechanical Relay | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
For Thermocouple Probe Type | Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | Reset Type | Input Voltage | NEMA Style | Cord Lg., ft. | Ht. | Wd. | Dp. | Environmental Rating | Each | |
J | 2 | Heating—Two Mechanical Relays | SPST-NO | 8 A @ 120 V AC | Automatic | 120V AC | 5-20 | 5 | 5" | 8 1/2" | 11" | IP50 | 00000000 | 000000000 |
K | 2 | Heating—Two Mechanical Relays | SPST-NO | 8 A @ 120 V AC | Automatic | 120V AC | 5-20 | 5 | 5" | 8 1/2" | 11" | IP50 | 00000000 | 00000000 |
High-Limit Temperature Controllers
To protect equipment and personnel, these controllers shut down your machine when it gets too hot. Reset them manually to turn your machine on again. They're often used as a fail-safe system and for triggering alarms.
Set the actuation point and adjust other settings with the keypad. To read the temperature, these controllers use a highly sensitive thermocouple probe (sold separately). They have one or two mechanical relays that actuate circuits directly. Mount them into instrumentation panels with DIN cutouts.
Controllers that are SPDT (single pole, double throw) can turn one circuit from off to on (normally open) or on to off (normally closed).
Controllers that are SPST-NO (single pole, single throw) can turn one circuit from off to on (normally open).
To mount 1/16 DIN controllers to a surface or DIN rail, add DIN-rail/surface-mount adapters. To convert larger cutouts to fit 1/16 DIN controllers, add DIN cutout adapters.
For technical drawings and 3-D models, click on a part number.
Mechanical Relay | |||||||||
---|---|---|---|---|---|---|---|---|---|
Total No. of Outputs | Output Type | Industry Designation | Max. Switching Current @ Voltage | For Probe Type | Reset Type | Input Voltage Range | Environmental Rating | Each | |
1/16 DIN—For 1 3/4" Ht. x 1 3/4" Wd. Panel Cutout | |||||||||
2 | Heating—Two Mechanical Relays | SPST-NO SPDT | 2 A @ 240 V AC | Thermocouple | Manual | 90V AC to 264V AC | IP20, IP30 | 0000000 | 0000000 |
Mounting | ||||
---|---|---|---|---|
Fasteners Included | Screw Size | Number of Holes | Each | |
No | No. 6 | 2 | 000000000 | 000000 |