About Exhaust Fans
More
About Sound Levels
Measured in decibels (dB), volume ratings indicate how much noise equipment makes. Some common volume levels include a whisper @ 20 dB, a refrigerator @ 40 dB, a conversation @ 60 dB, and a light machine shop @ 90 dB. OSHA recommends hearing protection for exposure to 80 dB and greater.
Hazardous Location Exhaust Fans

These fans have a motor that is UL listed for hazardous environments. Use them to draw stagnant and humid air out of a room or area.
Direct-drive fans have fewer moving parts than belt-drive fans for less maintenance. Add a collar (sold separately) to connect a wall-mount fan these fans to a louver.
Belt-drive fans are quieter and last longer than direct-drive fans because their components can be replaced if they’re worn or damaged. They come with collars, so you can connect these fans to a louver.
Fans that cannot be sold to California do not meet energy efficiency requirements.
For technical drawings and 3-D models, click on a part number.
Fans | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Overall | Collars | |||||||||||||||||
Blade Dia. | Airflow, cfm | Volume | Drive Type | Motor Speed, rpm | No. of Speeds | Power, hp | Ht. | Wd. | Dp. | Housing Material | Blade Material | Environmental Rating | Includes | Cannot Be Sold To | Each | Each | ||
120/230V AC, Single Phase—Hardwire | ||||||||||||||||||
12" | 1,600 | Not Rated | Direct | 1,725 | 1 | 1/4 | 16 1/8" | 16 1/8" | 17 3/4" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | __ | __ | 0000000 | 000000000 | 0000000 | 0000000 |
16" | 2,800 | 61 dBA @ 15 ft. | Direct | 1,725 | 1 | 1/3 | 20 1/8" | 20 1/8" | 15" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | __ | __ | 0000000 | 00000000 | 0000000 | 000000 |
20" | 4,800 | 73 dBA @ 5 ft. | Direct | 1,725 | 1 | 1/2 | 24 1/8" | 24 1/8" | 19 1/2" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | __ | __ | 0000000 | 00000000 | 0000000 | 000000 |
24" | 6,500 | 71 dBA @ 5 ft. | Direct | 1,125 | 1 | 3/4 | 30 1/8" | 30 1/8" | 29 1/8" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D | __ | __ | 0000000 | 00000000 | 0000000 | 000000 |
30" | 9,840 | 71 dBA @ 10 ft. | Belt | 1,725 | 1 | 3/4 | 34 3/4" | 34 3/4" | 30" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | Collar | __ | 0000000 | 00000000 | 000000 | 00 |
36" | 11,000 | 72 dBA @ 10 ft. | Belt | 1,725 | 1 | 3/4 | 40 3/4" | 40 3/4" | 30" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | Collar | __ | 0000000 | 00000000 | 000000 | 00 |
42" | 14,600 | 74 dBA @ 10 ft. | Belt | 1,725 | 1 | 3/4 | 46 3/4" | 46 3/4" | 30" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | Collar | __ | 0000000 | 00000000 | 000000 | 00 |
48" | 19,100 | 70 dBA @ 10 ft. | Belt | 1,725 | 1 | 3/4 | 52 3/4" | 52 3/4" | 30" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | Collar | __ | 0000000 | 00000000 | 000000 | 00 |
230/460V AC, Three Phase—Hardwire | ||||||||||||||||||
20" | 4,800 | 73 dBA @ 5 ft. | Direct | 1,725 | 1 | 1/2 | 24 1/8" | 24 1/8" | 19 1/2" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | __ | __ | 0000000 | 00000000 | 0000000 | 000000 |
30" | 11,000 | 77 dBA @ 5 ft. | Direct | 1,125 | 1 | 1 1/2 | 36 1/8" | 36 1/8" | 29 1/4" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | __ | CA | 0000000 | 00000000 | 0000000 | 000000 |
36" | 15,500 | 80 dBA @ 5 ft. | Direct | 1,125 | 1 | 2 | 42 1/8" | 42 1/8" | 29 3/4" | Steel | Aluminum | NEC Class I Divisions 1, 2 Group D; NEC Class II Divisions 1, 2 Groups F, G | __ | CA | 0000000 | 00000000 | 0000000 | 000000 |
Hazardous Location Upblast Roof-Mount Exhaust Fans

With a UL-listed motor, these fans can be used in hazardous environments with combustible gases and dust to draw stagnant and humid air out through your roof, forcing it up and away from its surface.
Direct-drive fans have fewer moving parts than belt-drive fans for less maintenance.
Belt-drive fans are quieter and last longer than direct-drive fans because their components can be replaced if they’re worn or damaged.
For technical drawings and 3-D models, click on a part number.
Fans | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Overall | Mounting Bases | ||||||||||||||
Blade Dia. | Airflow @ Static Pressure | Volume | Motor Speed, rpm | Power, hp | Dia. | Ht. | Base Wd. | Wt., lbs. | Max. Ambient Temp., °F | Housing Material | Environmental Rating | Each | Each | ||
Totally Enclosed Motor Enclosure | |||||||||||||||
120/240V AC, Single Phase—Hardwire | |||||||||||||||
24" | 3,900 cfm @ 1/2 in. of H₂O 6,900 cfm @ 0 in. of H₂O | 75 dBA @ 5 ft. | 1,150 | 3/4 | 33" | 25" | 36" | 340 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 000000000 | 0000000 | 0000000 |
30" | 5,900 cfm @ 1/2 in. of H₂O 9,350 cfm @ 0 in. of H₂O | 72 dBA @ 5 ft. | 1,150 | 1 | 39" | 28" | 42" | 370 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 00000000 | 0000000 | 000000 |
240/460V AC, Three Phase—Hardwire | |||||||||||||||
36" | 15,700 cfm @ 1/2 in. of H₂O 21,000 cfm @ 0 in. of H₂O | 79 dBA @ 5 ft. | 1,150 | 3 | 45" | 31" | 48" | 480 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 00000000 | 0000000 | 000000 |
42" | 19,400 cfm @ 1/2 in. of H₂O 25,300 cfm @ 0 in. of H₂O | 80 dBA @ 5 ft. | 1,150 | 3 | 51" | 34" | 54" | 520 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 00000000 | 0000000 | 000000 |
48" | 31,600 cfm @ 1/2 in. of H₂O 36,200 cfm @ 0 in. of H₂O | 89 dBA @ 5 ft. | 1,150 | 7 1/2 | 57" | 37" | 60" | 670 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 00000000 | 0000000 | 000000 |
Fans | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Overall | Mounting Bases | ||||||||||||||
Blade Dia. | Airflow @ Static Pressure | Volume | Motor Speed, rpm | Power, hp | Dia. | Ht. | Base Wd. | Wt., lbs. | Max. Ambient Temp., °F | Housing Material | Environmental Rating | Each | Each | ||
Totally Enclosed Motor Enclosure | |||||||||||||||
120/240V AC, Single Phase—Hardwire | |||||||||||||||
24" | 3,530 cfm @ 1/2 in. of H₂O 6,150 cfm @ 0 in. of H₂O | 71 dBA @ 5 ft. | 1,750 | 3/4 | 33" | 25" | 36" | 340 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 000000000 | 0000000 | 0000000 |
30" | 2,950 cfm @ 1/2 in. of H₂O 9,800 cfm @ 0 in. of H₂O | 68 dBA @ 5 ft. | 1,750 | 3/4 | 39" | 28" | 42" | 410 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 00000000 | 0000000 | 000000 |
240/460V AC, Three Phase—Hardwire | |||||||||||||||
36" | 20,200 cfm @ 1/2 in. of H₂O 24,100 cfm @ 0 in. of H₂O | 82 dBA @ 5 ft. | 1,750 | 5 | 45" | 31" | 48" | 590 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 00000000 | 0000000 | 000000 |
42" | 22,400 cfm @ 1/2 in. of H₂O 27,800 cfm @ 0 in. of H₂O | 78 dBA @ 5 ft. | 1,750 | 5 | 51" | 34" | 54" | 720 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 00000000 | 0000000 | 000000 |
48" | 28,600 cfm @ 1/2 in. of H₂O 36,700 cfm @ 0 in. of H₂O | 80 dBA @ 5 ft. | 1,750 | 5 | 57" | 37" | 60" | 840 | 100° | Steel | NEC Class I Divisions 1, 2 Groups C, D; NEC Class II Divisions 1, 2 Groups E, F, G | 0000000 | 00000000 | 0000000 | 000000 |
Hazardous Location Equipment-Cooling Fan Kits
Cool electronics and other sensitive equipment in potentially unsafe areas. These fans are non-sparking, so they’re safe for use around gas and explosive dust. They also withstand washdowns, occasional submersion in water, and wet weather. They’re not for use in mines. Ball bearings reduce the heat that’s generated to prolong fan lifespan.
For technical drawings and 3-D models, click on a part number.

Overall | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Height | Width | Depth | Airflow, cfm | Temp. Range, °F | Volume, dBA | Current, A | Frame Material | Mounting Fasteners Included | Mounting Hole Diameter | Environmental Rating | Specifications Met | Each | |
With 304 Stainless Steel Fan Guard | |||||||||||||
120V AC, Single Phase, 50Hz/60Hz—Two Prong Plug | |||||||||||||
4.72" (120 mm) | 4.72" (120 mm) | 1.5" (38 mm) | 106 | 0° to 155° | 43 | 0.08 | Aluminum | No | 0.17" (4.3 mm) | IEC Zone 2 Groups IIC, IIB, IIA, IP68 | ATEX II 3 G Ex nA IIC Gc, C-UL Listed, UL Listed, UL Recognized Component | 0000000 | 0000000 |

Overall | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Height | Width | Depth | Airflow, cfm | Temp. Range, °F | Volume, dBA | Current, A | Frame Material | Mounting Fasteners Included | Mounting Hole Diameter | Environmental Rating | Specifications Met | Each | |
With 304 Stainless Steel Fan Guard | |||||||||||||
120V AC, Single Phase, 50Hz/60Hz—Two Prong Plug | |||||||||||||
5.91" (150 mm) | 6.77" (172 mm) | 2.01" (51 mm) | 220 | 0° to 155° | 57 | 0.23 | Aluminum | No | 0.17" (4.3 mm) | IEC Zone 2 Groups IIC, IIB, IIA, IP68 | ATEX II 3 G Ex nA IIC Gc, C-UL Listed, UL Listed, UL Recognized Component | 0000000 | 0000000 |