About Backflow-Prevention Valves
More
Flange-Mount Check Valves
- For Use With: Air, Argon, Helium, Krypton, Neon, Water, Xenon
- Disc Material: Bronze
- Seal Material: Buna-N Rubber
Sandwich these valves between two ANSI flanges for backflow prevention at a fraction of the weight of flanged check valves and a reduced pipeline footprint. ANSI flanges are sold separately. All valves open to allow flow in one direction and close when flow stops or reverses.
Flow coefficient (Cv) is the amount of water (in gallons per minute) at 60° F that will flow through a fully open valve with a difference of 1 psi between the inlet and the outlet.
For technical drawings and 3-D models, click on a part number.
Pipe Size | Flow Coefficient (Cv) | Max. Pressure | Min. Opening Pressure, psi | Temperature Range, °F | End-to-End Lg. | For Flange Class | Each | |
Cast Iron Body | ||||||||
---|---|---|---|---|---|---|---|---|
Flanged × Flanged | ||||||||
4 | 340 | 200 psi @ 70° F | 1.25 | -20° to 250° | 2 1/2" | 125 | 0000000 | 0000000 |
Compact Flange-Mount Check Valves
- For Use With: Air, Argon, Helium, Krypton, Neon, Water, Xenon
- Piston Material: 316 Stainless Steel
- Spring Material: 316 Stainless Steel
- Seal Material: Viton® Fluoroelastomer
Less than half the end-to-end length of standard flange-mount check valves, these can be installed between ANSI flanges in pipelines with limited clearance. ANSI flanges are sold separately. Valves open to allow flow in one direction and close when flow stops or reverses. All have a 316 stainless steel body for excellent corrosion resistance.
Flow coefficient (Cv) is the amount of water (in gallons per minute) at 60° F that will flow through a fully open valve with a difference of 1 psi between the inlet and the outlet.
For technical drawings and 3-D models, click on a part number.
Pipe Size | Flow Coefficient (Cv) | Max. Pressure | Min. Opening Pressure, psi | Temperature Range, °F | End-to-End Lg. | For Flange Class | Each | |
316 Stainless Steel Body | ||||||||
---|---|---|---|---|---|---|---|---|
Flanged × Flanged | ||||||||
4 | 144 | 720 psi @ 100° F | 0.5 | -10° to 400° | 3/8" | 150, 300 | 0000000 | 0000000 |
Plastic Socket-Connect Check Valves
Also known as backwater valves, these valves prevent backflow of sewage and wastewater in drain, waste, and vent systems. Insert unthreaded pipe into the socket ends and bond with primer and cement to create a permanent, leak-tight connection. Valves open to allow flow in one direction and close when flow stops or reverses. A removable cap provides easy access to internal components for maintenance.
For technical drawings and 3-D models, click on a part number.
- For Use With: Water
- Pressure Class : Not Rated
- Disc Material: PVC Plastic
- Seal Material: PVC Plastic
Flanged Check Valves
- For Use With: Air, Steam, Water
- Disc Material:
Pipe Size 4 and smaller: Bronze
Pipe Size 5 and larger: Iron - Seal Material: Bronze
Bolt these valves to ANSI flanges. They open to allow flow in one direction and close when flow stops or reverses. All have a removable cap that provides easy access to internal components for maintenance.
Flow coefficient (Cv) is the amount of water (in gallons per minute) at 60° F that will flow through a fully open valve with a difference of 1 psi between the inlet and the outlet.
For technical drawings and 3-D models, click on a part number.
Pipe Size | Flow Coefficient (Cv) | Pressure Class | Max. Pressure | Max. Steam Pressure | Min. Opening Pressure | Temperature Range, °F | End-to-End Lg. | Flange OD | No. of Bolt Holes | Bolt Hole Size | Bolt Circle Dia. | Bolts Included | Includes | Each | |
Cast Iron Body | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Flanged × Flanged | |||||||||||||||
4 | 468 | 125 | 200 psi @ 70° F | 125 psi @ 353° F | 1 psi | -20° to 405° | 11 1/2" | 9" | 8 | 5/8" | 7 1/2" | No | Removable Cap | 0000000 | 0000000 |
Threaded Check Valves for Harsh Chemicals
These valves open to allow flow in one direction and close when flow stops or reverses.
Valves for drinking water meet NSF/ANSI Standard 61.
Polypropylene valves are more corrosion resistant than PVC or CPVC valves.
Flow coefficient (Cv) is the amount of water (in gallons per minute) at 60° F that will flow through a fully open valve with a difference of 1 psi between the inlet and the outlet.
- For Use With: Air, Butane, Carbon Dioxide, Citric Acid, Deionized Water, Diesel Fuel, Drinking Water, Ethanol, Ethylene Glycol, Hydrochloric Acid, Isopropyl Alcohol, Kerosene, Methanol, Mineral Spirits, Natural Gas, Oil, Oxygen, Phosphoric Acid, Propane, Salt Water, Soap Solutions, Sodium Hydroxide, Sodium Hypochlorite, Water
- Ball Material: PVC Plastic
- Seal Material: Fluoroelastomer Rubber
Pipe Size | Flow Coefficient (Cv) | Max. Pressure | Min. Opening Pressure, psi | Temperature Range, °F | Color | End-to-End Lg. | Specifications Met | Each | |
NPT Female × NPT Female | |||||||||
---|---|---|---|---|---|---|---|---|---|
4 | 400 | 150 psi @ 70° F | 1.5 | 35° to 140° | Dark Gray | 12 15/16" | ASTM D1784, NSF/ANSI 61 | 0000000 | 0000000 |
- For Use With: Air, Butane, Carbon Dioxide, Citric Acid, Deionized Water, Diesel Fuel, Drinking Water, Hydrochloric Acid, Isopropyl Alcohol, Kerosene, Mineral Spirits, Natural Gas, Nitric Acid, Oxygen, Phosphoric Acid, Propane, Salt Water, Soap Solutions, Sodium Hydroxide, Sodium Hypochlorite, Sulfuric Acid, Water
- Ball Material: CPVC Plastic
- Seal Material: Fluoroelastomer Rubber
Pipe Size | Flow Coefficient (Cv) | Max. Pressure | Min. Opening Pressure, psi | Temperature Range, °F | Color | End-to-End Lg. | Specifications Met | Each | |
NPT Female × NPT Female | |||||||||
---|---|---|---|---|---|---|---|---|---|
4 | 400 | 150 psi @ 70° F | 1.5 | 35° to 190° | Dark Gray | 12 15/16" | ASTM D1784, NSF/ANSI 61 | 0000000 | 000000000 |
Heavy Duty Threaded Check Valves for Drinking Water
- For Use With: Drinking Water
- Piston Material: Polyetherimide Plastic
- Spring Material: 302 Stainless Steel
- Seal Material: Buna-N Rubber
For more durability than plastic, these valves have a metal body. They meet NSF/ANSI 61 for drinking water service. All open to allow flow in one direction and close when flow stops or reverses.
Flow coefficient (Cv) is the amount of water (in gallons per minute) at 60° F that will flow through a fully open valve with a difference of 1 psi between the inlet and the outlet.
For technical drawings and 3-D models, click on a part number.
Pipe Size | Flow Coefficient (Cv) | Max. Pressure | Min. Opening Pressure, psi | Temperature Range, °F | End-to-End Lg. | Each | |
Brass Body | |||||||
---|---|---|---|---|---|---|---|
NPT Female × NPT Female | |||||||
4 | 225.4 | 400 psi @ 180° F | 0.5 | 10° to 210° | 5 7/16" | 0000000 | 0000000 |
Flange-Mount Check Valves for Drinking Water
- For Use With: Drinking Water
- Disc Material: 316 Stainless Steel
- Spring Material: 302 Stainless Steel
- Seal Material: EPDM Rubber
Sandwich these valves between ANSI flanges in drinking water pipelines. ANSI flanges are sold separately. Valves meet NSF/ANSI Standard 61, which designates them as safe to use with drinking water. All open to allow flow in one direction and close when flow stops or reverses.
Flow coefficient (Cv) is the amount of water (in gallons per minute) at 60° F that will flow through a fully open valve with a difference of 1 psi between the inlet and the outlet.
For technical drawings and 3-D models, click on a part number.
Pipe Size | Flow Coefficient (Cv) | Max. Pressure | Min. Opening Pressure, psi | Temperature Range, °F | End-to-End Lg. | For Flange Class | Each | |
Iron Body | ||||||||
---|---|---|---|---|---|---|---|---|
Flanged × Flanged | ||||||||
4 | 340 | 200 psi @ 300° F | 2 | 0° to 200° | 2 1/2" | 125, 150 | 000000 | 0000000 |
Flange-Mount Check Valves for Oil and Fuel
- For Use With: Butane, Diesel Fuel, Fuel Oil, Gasoline, Kerosene, Natural Gas, Oil, Propane
- Disc Material: 316 Stainless Steel
- Seal Material: 316 Stainless Steel
Install these valves between ANSI flanges. ANSI flanges are sold separately. All valves open to allow flow in one direction and close when flow stops or reverses. Body is 316 stainless steel for excellent corrosion resistance.
Flow coefficient (Cv) is the amount of water (in gallons per minute) at 60° F that will flow through a fully open valve with a difference of 1 psi between the inlet and the outlet.
For technical drawings and 3-D models, click on a part number.
Pipe Size | Flow Coefficient (Cv) | Max. Pressure | Min. Opening Pressure, psi | Temperature Range, °F | End-to-End Lg. | For Flange Class | Each | |
316 Stainless Steel Body | ||||||||
---|---|---|---|---|---|---|---|---|
Flanged × Flanged | ||||||||
4 | 291 | 275 psi @ 70° F | 1.25 | -20° to 1000° | 2 7/8" | 150, 300 | 0000000 | 0000000 |
Floor Drain Backflow Preventers
Put an end to water damage from backed-up sewers. To install, place a preventer into your floor drain pipe and tighten the screws—the rubber collar will expand for proper fit. When water backs up, the rubber float will rise to seal off the drain. When water recedes, the float will drop for normal drainage.
For Pipe Size | Each | |
4 | 0000000 | 000000 |